Motorized valve

                                                                                                                                                  
V20 series Motorized  valve V40 series Motorized three-line two-way valve
V60 often close type Motorized valve
 
                                                               V20 series Motorized  valve
                                                                                                                                                 
                                                                                        

                                                 Figure  1                                                                                 Figure  2

Introduction:

V20series electrical valve is used for opening and shutting down pipeline in the central air-conditioning system and the heating system, achieves the goal of controlling constant room temperature. The control valve drives by the unidirectional magnetic lag synchronous motor, the spring repositions. When the valve does not work is often in close condition, when needs to work, open the valve signal provides by thermostat, causes the motorized valve connect to the alternating current and work, opens the valve, the freezing water or the hot water enters the blower fan scroll, provides cold air and warm air for the room; When the room temperature achieves the thermostat’s set temperature, thermostat makes the motorized valve power off, the recoil check spring causes the valve close, thus interrupts the entering current water to blower fan scroll. By shutting down and opening of the valve, makes the room temperature maintain at the set temperature range. V20 series motorized valve may select and match auxiliary switch, applies to other control equipments; And may select different pipe connections to be suitable to the voltage, meets the different needs. V20 series motorized valve, operates nimbly, reliable and durable, low work noise, and can endure the high temperature environment which often appears in the hidden blower fan scroll.

Valve body material: Forging brass Valve lever material: Brass Airproof material: Butadiene acrylonitrile rubber (NBR) Actuators chassis: Stainless steel Driver lid: Aluminum alloy.


Specifications:

Valve Size Connection Type 2-way Cv(Kv) 3-way Cv(Kv) Close off ΔP PSI(KPa)
1/2" NPT, SW, SAE 1.0(0.9) 1.5(30) 75(517)
3/4" IFL
1/2" NPT, SW, SAE 2.5(2.2) 3.0(2.6) 50(344)
3/4" NPT, SW,  IFL
1/2" NPT, SW, SAE 3.5(3.0) 4.0(3.4) 30(208)
3/4" NPT, SW, IFL
1" SW
3/4" NPT, SW 5.0(4.3) 5.0(4.3) 25(172)
1" SW
3/4" NPT, SW 7.5(6.5) 7.5(6.5) 20(137)
1" NPT, SW 8.0(6.9) 8.0(6.9) 20(137)
1-1/4" SW

Outside dimension:

Valve Body Size Dimension (mm)
A (mm) B (mm) C (mm) D (mm)
1/2" Sweat 66 23 33 83
3/4" Sweat 70 23 43 83
1" Sweat 86 23 43 83
1-1/4" Sweat 94 25 46 83
1/2" NPT 70 23 33 83
3/4" NPT 86 23 37 83
1" NPT 94 25 43 83
IFL (Inverted Flare) see figure 2

Nomenclature